Error codes
This page explains the codes that the gateway, the opcua-omni-edge check command, VS Code and the browser editor show.
The code is at the start of each message, for example MAP-E001.
The letter E marks an error: the gateway does not start, or the editor refuses the entry. The letter W marks a warning: the gateway starts and writes the message in its log.
Configuration file (CONFIG)
The gateway checks the configuration file against the schema before it starts.
| Code | Meaning | What to do |
|---|---|---|
CONFIG-E001 | The configuration file does not match the schema. The message lists each problem with the path of the entry, for example /instances/1. The gateway does not start. | Correct each listed problem. Look up any other code in the message on this page. See Configuration. |
Server options (SRV)
These codes come from the serverOptions: section. The schema cannot check these rules, so a separate check reports them.
| Code | Meaning | What to do |
|---|---|---|
SRV-E001 | An advertised URL is not an opc.tcp:// URL with a host. | Write the URL as opc.tcp://host:4840. See Server. |
SRV-E002 | The resource path of an advertised URL is not the same as serverOptions.resourcePath. | Set resourcePath to the path of the URL. See Server. |
SRV-E003 | serverOptions.resourcePath does not start with /. | Add / at the start of the value. See Server. |
SRV-E004 | A host or port setting has a ${name} placeholder that the gateway does not know. Only ${hostname} and ${port} are replaced. | Use ${hostname} or ${port}, or write the value in full. See Server. |
Mapping entries (MAP)
These codes come from the entries of mapping:. Each entry needs exactly one source key.
| Code | Meaning | What to do |
|---|---|---|
MAP-E001 | A mapping entry has no source key. It names the node but not what feeds the node. | Add one source key: s7:, modbus:, ethernetIp:, value:, file: or folder:. See Mappings. |
MAP-E002 | A mapping entry has more than one source key. | Split the entry into one entry for each source, or delete the keys that you do not need. See Mappings. |
MAP-E003 | The gateway has no installer for the type of a mapping entry. The message says this is a gateway defect and not a configuration error. | Report the defect to Sterfive with the configuration file. |
Inputs and links (INPUT)
These codes come from the inputs: of a value: entry and from the address of a modbus: entry.
The address has the form <connection>:<address>.
| Code | Meaning | What to do |
|---|---|---|
INPUT-E001 | The address of an input is empty. | Write the address of the input as <connection>:<address>. |
INPUT-E002 | The address of an input does not start with a connection name. | Start the address with the connection name and :. |
INPUT-E003 | The connection name of an input is used for more than one connection, so the gateway cannot find the protocol. | Give each connection a different name:. |
INPUT-E004 | The Modbus address of an input has a table or an address that the gateway cannot read. The message gives the reason. | Write the address as <table>:<address>, for example holding:12. See Modbus. |
INPUT-E005 | A raw Modbus address of a coil or discrete table has a machine type. A bit has no machine type. | Remove the machine type from the address. |
INPUT-E006 | A raw Modbus address of a register has no machine type. | Add a machine type, for example holding:10,int16. Or name a point: <connection>:<pointName>. |
INPUT-E007 | The connection has no point with the name that the input uses. The message lists the points that the connection has. | Correct the point name, or add the point to points: of the connection. |
INPUT-E008 | The point that the input names has no at: key. | Add at: to the point. |
INPUT-E009 | No device connection has the name that the input uses. The message lists the declared connection names. | Correct the connection name, or add the connection to brownfieldDevices:. |
INPUT-E010 | The address of an input for a non-Modbus connection has nothing after the connection name and :. | Write the address after the :. |
INPUT-E011 | The name of an input is not a plain identifier. The formula must refer to it as $name. | Use letters, digits and _ only. Do not start the name with a digit. |
INPUT-E012 | The point that the input names is on a register table and has no type:. The gateway cannot decode the registers. | Add type: to the point. |
INPUT-E013 | The gateway has no jsonata accessor for the protocol of an input. The message calls this a wiring defect. | Report the defect to Sterfive with the configuration file. |
INPUT-E014 | The gateway started a value: entry with inputs:, or a modbus: entry, without its configuration. The gateway cannot resolve the connection names. | Report the defect to Sterfive with the configuration file. |
INPUT-E015 | A raw Modbus address is not in the registers that the connection polls. The poll plan comes from points:. | Declare a point at this address and use its name: <connection>:<pointName>. See S7. |
INPUT-E016 | A modbus: entry names a connection that is not a Modbus connection. | Name a Modbus connection in the modbus: entry. |
INPUT-E017 | A modbus: entry names a point that has a conversion. A direct link reads the raw register, so it publishes a wrong number. | Publish the point with expose:. Or use a value: entry with inputs: and do the arithmetic in value:. |
INPUT-E018 | A modbus: entry reads a register with a machine type that the gateway cannot decode. The message lists the types that it can read. | Use a machine type from the list in the message. |
Modbus addresses (MODBUS)
This code comes from the schema. VS Code and the check command show it when the value of a modbus: key has a wrong form.
| Code | Meaning | What to do |
|---|---|---|
MODBUS-E001 | The value of modbus: is not <connection>:<pointName> and is not a raw address. | Write <connection>:<pointName>, or a raw address such as M1:holding:12,float32. A register needs a machine type. A bit, such as M1:coil:3, has none. See Modbus. |
Direction (DIR)
These codes come from the direction: key of a mapping entry.
The gateway reads devices only. A write fails, in the order of the rules below.
| Code | Meaning | What to do |
|---|---|---|
DIR-E001 | The entry sets direction: to write or both, but the gateway cannot calculate the value backwards. The message gives the reason. | Remove direction:, or follow the reason in the message. See Mappings. |
DIR-E002 | A link with scale: or offset: has inverse:. Only a computation uses inverse:. The gateway inverts a link by itself. | Remove inverse:. |
DIR-E003 | The entry sets direction: to write or both, but the access: of the Modbus point is RO. | Correct access: of the point, or correct direction: of the entry. |
DIR-E004 | The entry sets direction: to write or both. The gateway cannot write to a device today. The gateway does not start. | Remove direction:, or set it to read. See Mappings. |
DIR-E005 | The value of direction: is not read, write or both. | Use read, write or both. |
DIR-E012 | The entry writes to a Modbus raw address. A raw address has no access: for the gateway to check. | Declare the register in points: with its access:, and name the point in the entry. See Mappings. |
Scaling (SCALE)
These codes come from the scale: and offset: keys of a mapping entry.
| Code | Meaning | What to do |
|---|---|---|
SCALE-E001 | scale: is not a finite number. | Write a number for scale:. |
SCALE-E002 | scale: is zero. Every reading becomes the offset, and the gateway cannot invert the value. | Write a scale: that is not zero. |
SCALE-E003 | offset: is not a finite number. | Write a number for offset:. |
SCALE-E004 | The entry has scale: or offset:, but its node does not have a numeric data type. | Remove scale: and offset:, or use a node with a numeric data type. |
SCALE-E005 | A modbus: entry has scale: or offset:. Modbus scaling belongs to the point. | Move scale: and offset: to the point in points:. See Modbus. |
Modbus import (IMPORT)
These codes come from import: of a Modbus connection, which reads a vendor file, and from the binding of a mapping entry to its node.
Some of the codes with E are warnings in some cases. The message shows the real severity.
| Code | Meaning | What to do |
|---|---|---|
IMPORT-E000 | The editor failed in an unexpected way when it resolved the points of a connection. The message gives the cause. | Read the cause in the message. Report it if the configuration file is correct. |
IMPORT-E010 | The gateway cannot find the format of the file. | Set format: to the closest reader. See Modbus. |
IMPORT-E011 | The gateway cannot read the file of import:. Or import: needs a configuration directory, and the gateway did not load the configuration from a file. | Correct the file name. Load the configuration from a file. |
IMPORT-E012 | The file has a malformed row or element, or an unknown value. The gateway does not skip it. The message gives the line or the path. | Correct the row or element that the message names. |
IMPORT-E013 | An address of the file is out of range after the gateway sets the address base. | Correct the address in the file. |
IMPORT-E014 | The address base of the file is not sure. A SunSpec file starts its models at PDU address 40000. The gateway reports this as a warning. | Check the addresses with a preview read of the device before you use them. |
IMPORT-E021 | Two points collide. They have the same name, or they overlap on a table. Only points with bit: or bitmask: can share registers. | Rename a point, or change its address. |
IMPORT-E030 | A point does not fit its table. A value and its scaleRegister span more entries than the table cap. | Move the scale register closer to the value, or split the profile. |
IMPORT-E031 | A mapping entry or a point has a node that does not exist, or the connection has no target for its points. | Correct the browse path and the namespace aliases. Or add expose: to the connection, or node: to the point. See S7. |
IMPORT-E032 | The source has a construct that the gateway does not support, for example a BCD data type or an array address. | Remove the point from the import, or use a different format. See Modbus. |
IMPORT-E033 | A point has an access that its table does not allow, for example RW on a read-only table. | Correct access: of the point. |
IMPORT-E034 | A point is not consistent with itself, for example scaleRegister in another table, or a string without a length. The message gives the reason. | Correct the point as the message says. |
IMPORT-E035 | The poll plan needs more than 100% of the serial link. | Raise pollingRate, merge tables, or split the connection. |
IMPORT-W001 | The editor cannot read the import: of a connection. It cannot check the point names of this connection. | Correct the import: file. Then the editor checks the point names. |
IMPORT-W020 | A point in points: replaces an imported point. | Check that the replacement is what you want. See Modbus. |
IMPORT-W022 | A pattern of overrides: matches no point of the import. It does nothing. | Correct the pattern. See Modbus. |
IMPORT-W040 | The gateway imports writable points as read-only, because it cannot write to a Modbus device today. | Do nothing for a read. A write needs a point with access: that you declare by hand. |
IMPORT-W041 | The source file claims RW on a read-only table. | Correct the file, or ignore the warning. |
Folder entries (FOLDER)
These codes come from a folder: mapping entry. See File and folder.
| Code | Meaning | What to do |
|---|---|---|
FOLDER-E001 | A key of access: is not correct: an unknown key, a value that is not a list, or a role that the gateway cannot find. | Use the keys that the page of the folder entry lists. Write each role as a standard role name, a browse name or a node id. |
FOLDER-E002 | poll: of a folder entry is not a number of 1000 or more. | Write a number of milliseconds, 1000 or more. |
FOLDER-E003 | The gateway cannot apply access:, because its file transfer component is too old. The gateway does not start, so that the folder does not stay open. | Update the gateway. |
FOLDER-E004 | ignore: of a folder entry is not a list of patterns, or a pattern is empty or starts with #. | Write a list of texts, such as ["*.part", ".*"]. |
Event sources (EVT)
This code comes from the eventNotifier: key of an instance.
| Code | Meaning | What to do |
|---|---|---|
EVT-E001 | An instance has eventNotifier: true, but it is a Variable. An event source must be an Object. | Remove eventNotifier:, or make the instance an Object. |
Types (TYP)
This code comes from the address-space check of VS Code. The schema cannot find it, because the loaded model decides whether a type is abstract.
| Code | Meaning | What to do |
|---|---|---|
TYP-E001 | The typeDefinition: of an instance is an abstract type. The gateway cannot instantiate it. | Name a concrete subtype. |
Templates (TPL)
These codes come from the template expander of instances:. Each code has a sample in the error catalogue of the templates page.
| Code | Meaning | What to do |
|---|---|---|
TPL-E001 | use: names a template that templates: does not define. See the sample. | Correct the name, or add the template. |
TPL-E002 | An expression reads a name that is not in its scope. A template sees only its params and parent. See the sample. | Declare the value as a param, and give it in with: or in the record. |
TPL-E003 | A param without a default gets no value. See the sample. | Give the value in with: or in the record, or give the param a default. |
TPL-E004 | The same name comes from the with: of the block and from a record. See the sample. | Give the value one time only. |
TPL-E005 | A template uses itself, directly or through other templates. See the sample. | Remove the loop. |
TPL-E006 | A value does not have the type of its param, or is not in its enum list. See the sample. | Correct the value. |
TPL-E007 | A template takes a counter that no enclosing block declares in counters:. See the sample. | Declare the counter in counters: of an enclosing block. |
TPL-E008 | Two instances get the same browse path or the same node id after expansion. See the sample. | Give each instance a different browse name or node id. |
TPL-E009 | A $Name anchor names a browse name that the expansion gave to more than one instance. See the sample. | Anchor on a unique name, and walk down from it. |
TPL-E010 | jsonata cannot read or evaluate an expression, or the expression uses $now, $millis, $random or $eval. See the sample. | Correct the expression. An expansion must give the same result every time. |
TPL-E011 | A record, or the with: of a layout entry, gives a value for a param that the template does not declare. See the sample. | Correct the param name, or declare the param. |
TPL-E012 | repeat: does not give a whole number of zero or more. See the sample. | Write a whole number of zero or more. |
TPL-E013 | A table has a column that no param matches, or has no column for a required param. See the sample. | Rename the column, or add the column or the param. |
TPL-E014 | A cell of a table cannot be read as the type of its param. See the sample. | Correct the cell. |
TPL-E015 | The expander cannot read a table file. See the sample. | Correct the file name, or the file. |
TPL-E016 | A template or a block does not have the correct shape. See the sample. | Correct the shape as the message says. |
TPL-E017 | An override names a browse path or a node id that no instance has after expansion. See the sample. | Write the path as dump-config prints it, or write the node id. |
TPL-W001 | A value has more digits than its format. The expander keeps the value whole. See the sample. | Widen the format of the counter. |
TPL-W002 | A block that reads a table also uses index. A moved or added row changes every value after it. See the sample. | Put the value in a column of the table. |
Runtime nodes (RTN)
This code comes from the browser editor, when it is connected to a running gateway.
| Code | Meaning | What to do |
|---|---|---|
RTN-E001 | An instance has the browse name of a runtime node that already exists under the same parent. The gateway orphans the runtime node at its next start. | Rename the instance, or delete the runtime node first. |